Weidmuller PT 100/4 signal conditioners for voltage output Bedienungsanleitung Seite 1

Stöbern Sie online oder laden Sie Bedienungsanleitung nach Hardware Weidmuller PT 100/4 signal conditioners for voltage output herunter. Weidmuller PT 100/4 signal conditioners for voltage output User Manual Benutzerhandbuch

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 14
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 0
15
WAVESERIES
PT 100/4 Signal Conditioners
for Voltage Output
Type Cat. No.
Screw-type connection
WTS4 PT100/4 Select V 8432240000
Tension clamp connection
WTZ4 PT100/4 Select V 8432250000
Read these instructions before using the product
and retain for future information.
Seitenansicht 0
1 2 3 4 5 6 ... 13 14

Inhaltsverzeichnis

Seite 1

15WAVESERIESPT 100/4 Signal Conditionersfor Voltage OutputType Cat. No.Screw-type connectionWTS4 PT100/4 Select V 8432240000Tension clamp connectionWT

Seite 2

24DIP switchesSpan 4 5 640 ... 50 °C ON ON ON50 ... 75 °C ON ON OFF75 ... 110 °C ON OFF ON110 ... 165 °C ON OFF OFF165 ... 245 °C OFF ON ON245 ... 360

Seite 3

257 Notes on CE labelling of WAVESERIES modulesWAVESERIES modules, that carry CE-labelling, fulfil the require-ments of the EU-Guidelines 89/336/EU “e

Seite 4

26Input range -200 ... +800 °C adjustable usingDIP switchesOffset input range up to +25 % possibleOutputVoltage output 0 ... 10 VLoad resistance ≥ 1 k

Seite 5

27Connection dataConnection BLZ/SLInsulating stripping length 8 ± 0.5 mmSolid core 0.5 ... 2.5 mm2Flexible core 0.5 ... 2.5 mm2With ferrules 0.5 ... 1

Seite 6

289 AccessoriesCross-connection ZQV 2,5N/2 black 1718080000Cross-connection ZQV 2,5N/2 red 1717900000Cross-connection ZQV 2,5N/2 blue 1717990000Cross-

Seite 7

161 General instructionsThe WAVESERIES signal conditioner PT 100 should only beinstalled by qualified staff. The signal conditioner PT 100 shouldonly

Seite 8

173.1 Mounting onto TS 35 DIN rails(s. Fig. 1)3.2 Pluggable electronic components for range alteration(depending on model)(s. Fig. 2)1. Remove connect

Seite 9

183.4 Pluggable cross-connections for voltage supply(s. Fig. 4)A maximum feed through of 2 A is possible.If a signal conditioner is accidently rotated

Seite 10

194.2 Basic calibration with a signal output from 0 ... 10 V1. Select the temperature range on the printed circuit boardusing the DIP switch, see tabl

Seite 11

20ExampleInput range: -50 ... +150 °CMinimum input temperature: = -50 °CChoose next lower or equal value according to table for ϑmin.Table value -60 °

Seite 12

214.3 Linearity calibration1. Proceed with basic calibration, see above.2. Add 1 % of the temperature span to the selected "minimum"temperat

Seite 13

22ExampleChosen measurement -50 ... +150 °C → 200 K spanrange: 1 % from 200 K span = 2 KSet minimum temperature -50 °C + 2 K = -48 °Con the PT 100 sim

Seite 14

234.4 Setting the DIP switchesWarning!! The signal conditioner PT 100 must be protectedagainst a direct electrostatic discharge when settingthe DIP sw

Kommentare zu diesen Handbüchern

Keine Kommentare