7 Notes on CE labelling of WAVESERIES modules
WAVESERIES modules, that carry CE-labelling, fulfil the require-
ments of the EU-Guidelines 89/336/EU “electromagnetic compat-
ibility” and the therein listed harmonised European Norms (EN).
The declarations of conformity are, in accordance with the above-
mentioned EU-Guideline, Article 10, held at the following address
for the relevant authorities:
Weidmüller Interface GmbH & Co.
Postfach 3030
D-32720 Detmold
8 Technical data
Input
Sensor types PT 100/4 Select V according to DIN
IEC 751
Input current 1.35 mA ... 1.45 mA ... 1.60 mA
Connection type selection using DIP switches
Conductor resistance < 50 (3- and 4-wire connection)
Influence of conductor
resistance max. ± 0.005 °C/ for 3- and 4-wire
connection