39
• Analogue Input type Selection/Calibration
Input type selection
The AMS400A series instruments are factory calibrated to the range
ordered. If you have the necessary equipment, you can change the
input type and adjustment range by changing components according
to the table below. The Instrument will need recalibration.
Input Adjustment Range R1 R2 R3 R4
0-8 mA thru 0-24 mA 36R 68K Omit 120K
0-4 V DC thru 0-12 V DC Omit 1M 75K 120K
0-1 V DC Omit 68K Omit 82K
Analogue Input Calibration
Equipment requirements
• A suitable current or voltage source
T
erminal Connections for input calibration
Calibration Stage Signal type Terminal
Analogue Inputs
Signal source (+) 11
Signal source (−) 12
Procedure
Note: Allow 15 mins of powered operation before calibration.