Input calibration procedure
When the
display shows
Action/Description
ENT
ï
Put the instrument in setup mode and scroll through the main menu
C Pn
Press Å or ì
C Py
Calibrate inputs? Start No
Connect the signal source to the inputs (e.g.,mA current source for 4-20 mA input format).
InL=
Introduces the input low value Next -
4.00
Set the signal source to 4.00 mA Calibrate -
InH=
Introduces the input high value Next -
20.00
set the signal source to 20.00 mA Calibrate -
COPy
Continue with the setup sequence.
Note: To discard changes to calibration and setup you can remove the power at this point.
Terminal Connections for output calibration
Calibration Stage Signal type Terminal
Analogue Current Output
mA output + 14
mA output − 15
Analogue Voltage Output
V output + 14
V output − 16
Output calibration procedure
When the
display shows
Action/Description
ì Å
ENT
Put the instrument in setup mode and scroll through the main menu
COPn
Press Í
COPy
Calibrate Outputs? Toggle Start
Measure the output signal
OPL=
Introduces the output low value (in this example, 1 V
for a unit set-up for 1-5 V outputs)
- - Next
1.00
The output voltage should be 1.00V Increase Decrease Accept
OPH=
Introduces the output high value (in this example, 5 V
for a unit set-up for 1-5 V outputs)
- - Next
5.00
The output voltage should be 5.00 volts Increase Decrease Accept
Save
Instrument will save values and return to normal operation (using the new values).
Note: Do not remove the power while the save message is on display.