Connections
For effective protection from electromagnetic noise, all signal cables
must be shielded, or located on conductive trays or in conduits.
Use 12-28 AWG Cu Wire rated for temperatures above 70 °C Only,
tighten to 4.5 lb-In. Strip wires to 7 mm from the ends. Use a suitable
ferrule for multi-stranded wires (do not solder).
Terminal Signal
1
24 V DC (out)
Input signals
2
Current +
3
Common −
4
Voltage +
5
Not used
6
7
Link to change the set-up Security Link
8
9 Neutral (−)
Power supply
10 Live (+)
11 Normally Closed
Alarm Channel One
12 Common
13 Normally Open
14 Normally Closed
Alarm Channel Two
15 Common
16 Normally Open
Case Earthing is via a stud on lower side of case