4 Calibration
Warning!! The power supply must be disconnected, before
changing the signal conditioner settings using the
DIP switches.
Failure to observe will lead to considerable damage!
4.1 Equipment
Power supply 24 Vdc, 50 mA
Simulator for PT 100 or precision resistance decade
Current meter/voltmeter that can be so calibrated, as to allow
an accuracy of > 0.1 % from the upper range value
4.2 Calibration with a signal output from 0 ... 20 mA
1. Select the temperature range on the printed circuit board
using the DIP switch, see table on the module or pages 22
and 23.
The DIP switches 1, 2 and 3 set the minimum input tempera-
ture ϑ
min
.
The span (difference between minimum and maximum input
temperature) is set using the DIP switches 4, 5 and 6.