Weidmuller DC/DC CCC LP - without additional voltage supply Bedienungsanleitung Seite 5

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 8
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 4
13
7 Technical data
Input
Input signal 0 ... 20 mA (4 ... 20 mA)
Input voltage, max. 18 V
Input current, max. 50 mA
Operating current < 100 µA
Voltage drop approx. 3 V at R
L
= 0
at I
in
= 20 mA
approx. 13 V at R
L
= 500
at I
in
= 20 mA
Output
Output signal 0 ... 20 mA (4 ... 20 mA)
Load resistance 500
Accuracy by T
u
= 23 °C < 0.1 % from end value
Influence of the load resistance < 0.1 % from measurement per
100 load resistance
Temperature coefficient 50 ppm/K from measured value
Response time 4.5 ms by 500 burden
Remaining ripple < 20 mV
eff
Chopper frequency approx. 170 kHz
Seitenansicht 4
1 2 3 4 5 6 7 8

Kommentare zu diesen Handbüchern

Keine Kommentare