3.4.2 Set WI-MOD-E to same network as PC
This is the alternate procedure to setting an IP address in the WI-MOD-E. Consult your network
administrator for an IP address on your network, the gateway IP address, and network mask.
a) Switch Factory Default dip-switch on WI-MOD-E to SETUP position.
b) Connect the RS232 port on the WI-MOD-E to the RS232 port on the PC using a “straight-
through” serial cable.
c) Open a terminal package (such as HyperTerminal) with 19200bps data rate, 8 data bit, 1 stop,
no parity and no flow control. Make sure that no other programs have control of the serial port.
d) Power up WI-MOD-E. Basic network settings will be displayed on the terminal as illustrated
below. When prompted, hit enter key to stop automatic boot process. You have 5 seconds to
abort the boot process.