Weidmuller XFAR - Universal glavanically isolated signal conv Bedienungsanleitung Seite 17

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 28
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 16
17
Power Supply Requirements
Check the power supply against the model number before applying
power to the instrument. Units must be used with the specified mains
supply, ratings are as follows:
Voltage Range Nominal Voltage Power Frequency
100–132 V AC 110 V AC 6 VA 47-63 Hz
200264 V AC 240 V AC 6 VA 47-63 Hz
12–50 V DC* 24 V DC 5 W (at 24 V DC) -
*Using a DC power supply that provides this voltage will comply with
the instrument’s UL/CSA listing.
Connections
Strip wires to 7 mm from the ends. Use a suitable ferrule for multi-
stranded wires (do not solder).
Use 12-28 AWG Cu Wire rated for temperatures above 70 °C Only,
tighten to 4.5 lb-In.
Seitenansicht 16
1 2 ... 12 13 14 15 16 17 18 19 20 21 22 ... 27 28

Kommentare zu diesen Handbüchern

Keine Kommentare