Application Note WI-GTWY-9-DE1 DeviceNet Slave
Weidmuller
Page 9 of 16 App Note WI-GTWY-9-DE1 v1.1
After uploading, select the parameters tab to display the uploaded parameters. There will be 6
available input parameters and 6 output parameters. The offset and length parameters cannot be
modified here, but will correspond to the “I/O Instance” settings from W-Series Configuration
software. In the example below, Input 1 offset = 0 and length = 20 bytes. This corresponds to the
“fieldbus write mapping” to Input Instance 1 that was configured via W-Series Config Utility (see
WI-GTWY-9 configuration section). This mapping was for 10 words, or 20 bytes.
We now have to setup our connection instances. Looking at the illustration below, it can be seen
that a drop-down box allows selection of the available input or output instances for each connection
type. For example, here we choose ‘input 2’ (i.e. input instance 2) for the ‘COS Production’
connection. Input and Output instances 1 are chosen for Polled Production and Polled Consumption
respectively (as per the description in the summary section). Strobed Production and Consumption
will not be used, however they default to instance 1.
Once the desired configuration is made, click apply to download the changes to the WI-GTWY-9-
DE1.